§ C-108. International Mechanical Code  


Latest version.
  • 1.

    The administrative officer is the building official. All hearings, variances etc. are handled by the BSC.

    2.

    Add to Section M306.3: "There must be a permanently-installed stairway, either fixed or folding, to serve attic space where appliances or equipment are located. The opening must be at least 25.5" x 54", and any folding staircase must be rated for at least 350 pounds capacity and at least 20 minutes fire resistance."

    3.

    Add to Section M605.1: "All return air filters in new residential construction and wherever possible in existing buildings shall be installed within 24 inches of the finished floor or there must be installed a media-type or electrostatic-type air filter at the equipment."

    4.

    Delete: All appendices to the International Mechanical Code.

(Ord. No. 1775, § 1(app. A), 9-27-2004; Ord. No. 1823, § 1, 5-8-2006; Ord. No. 1896, § 1, 5-11-2009; Ord. 1963, § 1(exh. C), 10-22-2012)